FR / HR / FRLS / ZHFR
Insulated annealed copper conductor single core wire
Size in sq. mm. |
Size in mm. |
Approximate Dia in
mm. |
Max. D.C. Resistance @ 20o C |
Current Rating in Amp |
0.50 |
16 / 0.20 |
2.40 |
39.00 |
4 |
0.75 |
24 / 0.20 |
2.60 |
26.00 |
7 |
1.00 |
32 / 0.20 |
2.80 |
19.50 |
11 |
1.50 |
48/0.20 / 30/0.25 |
3.35 |
13.30 |
14 |
2.50 |
80/0.20 / 50/0.25 |
3.80 |
7.98 |
19 |
4.00 |
56 / 0.30 |
4.60 |
4.95 |
26 |
6.00 |
84 / 0.30 |
5.40 |
3.30 |
35 |
10.00 |
140/0.30 / 80/0.40 |
7.50 |
1.91 |
45 |
16.00 |
226/0.30 / 126/0.40 |
9.00 |
1.21 |
60 |
25.00 |
354/0.30 / 196/0.40 |
9.50 |
0.780 |
80 |
35.00 |
276 / 0.40 |
11.30 |
0.554 |
102 |
50.00 |
396 / 0.40 |
13.80 |
0.386 |
138 |
70.00 |
354 / 0.50 |
15.20 |
0.275 |
214 |
95.00 |
484 / 0.50 |
18.00 |
0.206 |
254 |
120.00 |
608 / 0.50 |
19.50 |
0.161 |
300 |
150.00 |
750 / 0.50 |
21.80 |
0.129 |
340 |
185.00 |
925 / 0.50 |
24.00 |
0.106 |
390 |
240.00 |
1210 / 0.50 |
— |
0.801 |
460 |
* Note insulation thickness, Sheath thickness and overall dimensions given in this table are nominal value. The strand diameter is nominal. However, Construction of the Conductor is designed to satisfy the requirement of conductor resistance as per IS 8130 : 1984