NBR/NBR 0.6/1kV 90°C

Premium Single Core Double Insulated. Extreme Flexibility Rubber Cable

Information

Technical Data
  • Operating Temp: -30°c to max.+90°C
  • Nominal voltage: 1100 V
  • Test voltage: 3000 V
  • Insulation resistance: Min. 10 MΩ x km
  • Min. bending radius: 6 x cable diameter
  • Flame propagation: Flame retardant test as per IEC 60332-1
Cable Structure

Generally conforming to CENELEC HD22.6, IEC 245-6, AS3147, IEC 60332-1 CE Directive 72/23/EEC

Conductor:
EC copper class 5 and class 6 generally conforms to IEC 60228, DIN VDE 0281

Insulation:
NBR

Sheath:
Flexible Nitrile rubber (NBR) Orange, Black, Red, Blue Jacket

*Any other Color on specific request can also be supplied

Cable features
  • Flame retardant. UV Stabilized. Heat, oil and chemical resistant
  • Ultra high performance flexible for longer life and added safety
  • High elasticity
  • Outstanding toughness & durability
  • High resistance to cuts, tears & abrasion
  • Excellent ozone and weather resistant
Application

NBR/NBR 0.6/1kV 90°C
For industrial uses, secondary side connection of power sources for metal arc welding, heavy duty portable supply in dry, wet and oil environments. For motor connections, generators transformers where flexible connections are required and all fixed wiring 0.6/1kV power applications.

Standard length cable packing:
Coils 100, 200,300 and 500 m. in wooden reels

Technical DataTable

NBR/NBR single core double insulated cable
NBR/NBR single core double insulated cable
Nominal cross sectional area of conductor Nominal insln thickness Nominal sheath thickness Overall cable diameter Max conductor resistance at 20°C
Lower limit Upper limit
sqmm mm mm mm mm Ω/km
10 1.2 1.8 7.8 10 1.91
16 1.2 1.9 9 11.5 1.21
25 1.4 2 10 13 0.780
35 1.4 2.2 11.5 14.5 0.554
50 1.6 2.4 13 17 0.386
70 1.6 2.6 15 19 0.272
95 1.8 2.8 17.5 21.5 0.206
120 1.8 3 19.5 24 0.161
150 2 3.2 21.5 26 0.129
185 2.2 3.4 23 29 0.106
240 2.4 3.5 27 32 0.0801
300 2.6 3.6 30 35 0.0641
400 2.8 3.8 33 39 0.0486
  • All are flexible conductor